Battery check

Will this panel's batteries carry the unit?

Pick the panel, enter its loops and add its cards. The check adds up the load, runs the battery sum with and without the Magnifire unit, and gives you a record to keep with the site.

1The site
Standby the site needs
2The batteries

Two 12 V batteries in series make 24 V at the capacity of one. Two 18 Ah batteries are 18 Ah, not 36.

3What the panel is running

Use + and − or type a number. Grey figures are typical values: type over them with the figure from the datasheet.

Quiescent
In alarm
4The Magnifire unit
standby, mobile data on
absolute peak, used for the alarm period

5Sign-off
The sum and its assumptions

Capacity = ageing × [ (quiescent × standby hours) + derating × (alarm × alarm hours) ]

Check these against the standard you design to before relying on the result.